For the unity-feedback system shown, with forward path containing: - An integrator: 1/s - A plant: 3/(s+4) - An inner feedback loop with gain 2 - An outer feedback path with gain 6s (i) Obtain the open loop transfer function G(s) for the system and hence determine the system type. (ii) Determine the position error constant K_p, velocity error constant K_v, and acceleration error constant K_a for the system. (iii) Calculate the steady-state error that may be expected for a unit ramp input.
Step-by-step solution with explanation
Final Answer
(i) Equivalent open-loop TF: — System Type 0 (no free integrators at s=0). (ii) , , . (iii) Steady-state error for unit ramp = (the Type 0 system cannot track a ramp input).Step-by-step solution
Understanding this problem
Learning Insight
System type tells you the highest-order input a system can track with finite error. A Type 0 system tracks only step inputs (with finite error), a Type 1 tracks ramps, and a Type 2 tracks parabolas. The number of integrators (poles at s=0) in the open-loop TF determines the type, because each integrator provides an automatic correction for one higher order of input. The outer feedback H(s)=6s acts like a derivative term, which actually removes the integrator's effectiveness for ramp tracking.Quick Tip
Quick pattern: count the bare 's' factors in the denominator of G_eq(s). That count IS the system type. Then: K_p needs Type≥0, K_v needs Type≥1, K_a needs Type≥2. Any constant below the required type is automatically zero, giving infinite steady-state error for that input.Common Mistake
Students often forget to convert to an equivalent unity-feedback open-loop TF when H(s)≠1. They mistakenly use G_forward(s) alone and count the integrator in it (giving Type 1), then wrongly compute a finite K_v. The outer feedback H(s)=6s cancels the integrator's benefit, making the system Type 0.